Thanks to its light weight and SnapINverter mounting system, this transformerless device can be installed quickly and easily either indoors or outdoors. This inverter range is setting new standards with its IP 66 protection class. Furthermore, thanks to its integrated double fuse holders and optional overvoltage protection, string collection boxes are no longer necessary.
INPUT DATA | |
---|---|
Max. input current (Idc max) |
175A |
Max. array short circuit current (Isc PV) |
250A |
Min. input voltage (Udc min) | 580 V |
Feed-in start voltage (Udc start) | 650 V |
Nominal input voltage (Udc,r) | 580 V |
Max. input voltage (Udc max) |
1,000 V |
MPP voltage range at Pnom (Umpp min - Umpp max) |
580 - 930 V |
Usable MPP voltage range | 580 - 930 V |
Number of MPP trackers | 1 |
Number of DC connections PV1/ PV2/ PV3 | 1 / 1/ - |
Max. PV generator output (Pdc max) | 150 kWpeak |
OUTPUT DATA | |
AC nominal output (Pac,r) | 100,000 W |
Max. output power | 100,000 VA |
AC output current (Iac no) | 152 A |
Grid connection (voltage range) | 3~NPE 380 V / 220 V or 3~NPE 400 V / 230 V (+20 % / -30 %) |
Frequency (frequency range) | 50 Hz / 60 Hz (45 - 65 Hz) |
Frequency range (fmin - fmax) | 45 - 65 Hz |
Power factor (cos φac,r) | 0 - 1 ind. / cap. |
GENERAL DATA | |
Dimensions (height x width x depth) |
755 x 1,109 x 346mm |
Weight | 103kg |
Degree of protection | IP 65 |
Protection class | IP 65 |
Night time consumption | < 16 W |
Inverter design | Transformerless |
Cooling | Active air cooling and doule wall system |
Installation | Indoor and outdoor installation |
Ambient temperature range | -40°C to +65°C |
Permitted humidity | 0 % to 100 % |
Max. altitude | 2,000 m |
DC connection technology | 25 mm² - 95 mm² |
AC connection technology | Cable lug or V clamps |
Certificates and compliance with standards | AS/NZS 4777.2:2020, IEC62109-1/-2, VDE-AR-N 4105:2018, IEC62116, EN50549-1:2019 & EN50549-2:2019, VDE-AR-N 4110:2018, CEI 0-16:2019, CEI 0-21:2019 |
EFFICIENCY | |
Max. efficiency | 98.5 % |
European efficiency (ηEU) | 98.2 % |
MPP adaption efficiency | > 99.9 % |
PROTECTIVE DEVICES | |
DC insulation measurement | Yes |
Overload behaviour | Operating point shift, power limitation |
DC disconnector | Yes |
Integrated string fuse holders3) | Yes |
Reverse polarity protection | Yes |
INTERFACES | |
WLAN / Ethernet LAN | Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON) |
6 inputs and 4 digital in/out | Interface to ripple control receiver |
USB (type A socket)4) | Datalogging, inverter update via USB flash drive |
2 x RS422 (RJ45 socket)4) | Fronius Solar Net, Interface protocol |
Wired Shutdown (WSD) | Emergency stop |
Datalogger and Webserver | Included |
RS485 | Modbus RTU SunSpec or meter connection |
Subject to modifications.