0 item(s)

Inverter FRONIUS Eco Tauro 100kW

Three-phase 27.0 kW

IP 66 protection class

 


SKU: tauro-eco-100-3-p
13714 €6,994.14 VAT included

Availability: Backorder

Delivery time: 8-30 days

Quantity:

It meets all the requirements of large-scale installations

Thanks to its light weight and SnapINverter mounting system, this transformerless device can be installed quickly and easily either indoors or outdoors. This inverter range is setting new standards with its IP 66 protection class. Furthermore, thanks to its integrated double fuse holders and optional overvoltage protection, string collection boxes are no longer necessary.

 

Technical Data


INPUT DATA 
Max. input current 
(Idc max)
175A
Max. array short circuit current
(Isc PV)
250A
Min. input voltage (Udc min) 580 V
Feed-in start voltage (Udc start) 650 V
Nominal input voltage (Udc,r) 580 V
Max. input voltage
(Udc max)
1,000 V
MPP voltage range at Pnom
(Umpp min - Umpp max)
580 - 930 V
Usable MPP voltage range 580 - 930 V
Number of MPP trackers 1
Number of DC connections PV1/ PV2/ PV3 1 / 1/ -
Max. PV generator output (Pdc max) 150 kWpeak
OUTPUT DATA 
AC nominal output (Pac,r) 100,000 W
Max. output power 100,000 VA
AC output current (Iac no) 152 A
Grid connection (voltage range) 3~NPE 380 V / 220 V or 3~NPE 400 V / 230 V (+20 % / -30 %)
Frequency (frequency range) 50 Hz / 60 Hz (45 - 65 Hz)
Frequency range (fmin - fmax) 45 - 65 Hz
Power factor (cos φac,r) 0 - 1 ind. / cap.
GENERAL DATA 
Dimensions
(height x width x depth)
755 x 1,109 x 346mm
Weight 103kg
Degree of protection IP 65
Protection class IP 65
Night time consumption < 16 W
Inverter design Transformerless
Cooling Active air cooling and doule wall system
Installation Indoor and outdoor installation
Ambient temperature range -40°C to +65°C
Permitted humidity 0 % to 100 %
Max. altitude 2,000 m
DC connection technology 25 mm² - 95 mm²
AC connection technology Cable lug or V clamps
Certificates and compliance with standards AS/NZS 4777.2:2020, IEC62109-1/-2, VDE-AR-N 4105:2018, IEC62116, EN50549-1:2019 & EN50549-2:2019, VDE-AR-N 4110:2018,
CEI 0-16:2019, CEI 0-21:2019
EFFICIENCY 
Max. efficiency 98.5 %
European efficiency (ηEU) 98.2 %
MPP adaption efficiency > 99.9 %
PROTECTIVE DEVICES 
DC insulation measurement Yes
Overload behaviour Operating point shift, power limitation
DC disconnector Yes
Integrated string fuse holders3) Yes
Reverse polarity protection Yes
INTERFACES 
WLAN / Ethernet LAN Fronius Solar.web, Modbus TCP SunSpec, Fronius Solar API (JSON)
6 inputs and 4 digital in/out Interface to ripple control receiver
USB (type A socket)4) Datalogging, inverter update via USB flash drive
2 x RS422 (RJ45 socket)4) Fronius Solar Net, Interface protocol
Wired Shutdown (WSD) Emergency stop
Datalogger and Webserver Included
RS485 Modbus RTU SunSpec or meter connection




Subject to modifications.