SUN2000-33KTL-A | |
---|---|
Efficiency | |
Max. Efficiency | 98.6% |
European Efficiency | 98.4% |
INPUT DATA | |
Max. Input Voltage 1 |
1,100 V |
Max. Current per MPPT | 22 A |
Max. Short Circuit Current per MPPT | 30 A |
Start Voltage | 250 V |
MPPT Operating Voltage Range 2 | 200 V ~ 1,000 V |
Rated Input Voltage | 620 V |
Number of MPP trackers | 4 |
Max. input number per MPP tracker | 2 |
OUTPUT DATA | |
Rated AC Active Power | 30,000 W |
Max. AC Apparent Power | 33,000 VA |
Max. AC Active Power | 30,000 W |
Rated Output Voltage | 3~NPE 400 V / 230 V or 3~NPE 380 V / 220 V (+20 % / -30 %) |
Rated AC Grid Frequency | 50 Hz / 60 Hz (45 - 65 Hz) |
Rated Output Current | 43.3 A |
Max. Output Current | 48 A |
Adjustable Power Factor Range | 0.8 leading... 0.8 lagging |
Max. Total Harmonic Distortion | <3% |
Protection | |
Input-side Disconnection Device | Yes |
Anti-islanding Protection | Yes |
AC Overcurrent Protection | Yes |
DC Reverse-polarity Protection | Yes |
PV-array String Fault Monitoring | Yes |
DC Surge Arrester | Type II |
AC Surge Arrester | Type II |
DC Insulation Resistance Detection | Yes |
Residual Current Monitoring Unit | Yes |
Communication | |
Display | LED indicators;WLAN adaptor + FusionSolarAPP |
RS485 | Yes |
USB | Yes |
Monitoring BUS (MBUS) | Yes (isolation transformer required) |
GENERAL DATA | |
Dimensions (height x width x depth) |
930 x 550 x 283 mm |
Weight | 62 kg |
Degree of protection | IP 65 |
Night time consumption | < 2.5 W |
Inverter design | Transformerless |
Cooling | Natural Convection |
Installation | Indoor and outdoor installation |
Ambient temperature range | -25°C to +60°C |
Permitted humidity | 0 % to 100 % |
Max, altitude | 4000 m |
DC connection technology | Amphenol Helios H4 |
AC connection technology | Waterproof PG Terminal + OT Connecto |
Certificates Grid Code |
EN 62109-1/-2, IEC 62109-1/-2, IEC 62116Grid CodeIEC 61727, VDE-AR-N-4105, VDE 0126-1-1, BDEW, G59/3, UTE C 15-712-1, CEI 0-16, CEI 0-21, RD 661, RD 1699, P.O. 12.3, RD 413, C10/11, EN 50438-Turkey, ABNT |
*1 The maximum input voltage is the upper limit of the DC voltage. Any higher input DC voltage would probably damage inverter
*2 Any DC input voltage beyond the operating voltage range may result in inverter improper operating
Subject to modifications.